Title:Non-destructive method for inward leakage detection of a plate evaporator
Authors:ID Hribernik, Aleš (Author)
Files:URL http://dx.doi.org/10.1088/0957-0233/18/5/049
 
Language:English
Work type:Unknown
Typology:1.01 - Original Scientific Article
Organization:FS - Faculty of Mechanical Engineering
Abstract:A new non-destructive method was developed for the detection of refrigerant leakage at an evaporator`s inflow. Nitrogen and oxygen gas were successively blown through the evaporator. A gas analyser was applied at the outflow of the evaporator and the oxygen concentration measured. It was possible to detect any leakage by investigating the oxygen concentration-time history diagram.
Keywords:refrigeration, refrigerant leakage, plate evaporator, measurements, non-destructive method
Year of publishing:2007
PID:20.500.12556/DKUM-25913 New window
UDC:621.57:620.179
ISSN on article:0957-0233
COBISS.SI-ID:11270422 New window
NUK URN:URN:SI:UM:DK:SKUX6WHQ
Publication date in DKUM:31.05.2012
Views:2018
Downloads:94
Metadata:XML DC-XML DC-RDF
Categories:Misc.
:
Copy citation
  
Average score:(0 votes)
Your score:Voting is allowed only for logged in users.
Share:Bookmark and Share



Hover the mouse pointer over a document title to show the abstract or click on the title to get all document metadata.

Record is a part of a journal

Title:Measurement science & technology
Shortened title:Meas. sci. technol.
Publisher:IOP Publishing
ISSN:0957-0233
COBISS.SI-ID:6000901 New window

Secondary language

Language:English
Keywords:hladilne naprave, uhajanje hladila, uparjevalnik, meritve, neporušitvena metoda


Comments

Leave comment

You must log in to leave a comment.

Comments (0)
0 - 0 / 0
 
There are no comments!

Back
Logos of partners University of Maribor University of Ljubljana University of Primorska University of Nova Gorica