Title:Izračun hladilnega sistema Kaplanove turbine : diplomsko delo
Authors:ID Harl, Nika (Author)
ID Iljaž, Jurij (Mentor) More about this mentor... New window
ID Urbas, Simon (Comentor)
Files:.pdf UN_Harl_Nika_2023.pdf (1,14 MB)
MD5: 3170D0E2D07F28442EF3DBB46025BD90
 
Language:Slovenian
Work type:Bachelor thesis/paper
Typology:2.11 - Undergraduate Thesis
Organization:FS - Faculty of Mechanical Engineering
Abstract:Cilj naloge je določiti najvišjo možno temperaturo reke Drave pri kateri je zaprt hladilni sistem še sposoben hladiti in držati agregat pod kritično temperaturo. Z izvedbo analitičnega preračuna smo preverili sposobnost hlajenja temperaturno najobčutljivejšega dela turbinskega sistema (nosilnega ležaja) in na podlagi dobljenih rezultatov predlagali možne izboljšave. Ugotovili smo, da je najvišja temperatura reke Drave, pri kateri je še mogoče nemoteno obratovanje brez kakršnihkoli sprememb hladilnega sistema 22,5 °C. V primeru, da bi povečali število plošč ploščnega toplotnega prenosnika nosilnega ležaja in pretok hladilne tekočine, bi lahko zagotovili ustrezno hlajenje agregata tudi pri temperaturi rečne vode 24 °C.
Keywords:Kaplanova turbina, zaprt hladilni sistem, ploščni toplotni prenosnik
Place of publishing:Maribor
Place of performance:Maribor
Publisher:[N. Harl]
Year of publishing:2023
Number of pages:1 spletni vir (1 datoteka PDF (XIII, 28 f.)
PID:20.500.12556/DKUM-84473 New window
UDC:621.224.35(043.2)
COBISS.SI-ID:158539523 New window
Publication date in DKUM:06.07.2023
Views:647
Downloads:175
Metadata:XML DC-XML DC-RDF
Categories:KTFMB - FS
:
Copy citation
  
Average score:(0 votes)
Your score:Voting is allowed only for logged in users.
Share:Bookmark and Share



Hover the mouse pointer over a document title to show the abstract or click on the title to get all document metadata.

Licences

License:CC BY-NC-ND 4.0, Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International
Link:http://creativecommons.org/licenses/by-nc-nd/4.0/
Description:The most restrictive Creative Commons license. This only allows people to download and share the work for no commercial gain and for no other purposes.
Licensing start date:12.06.2023

Secondary language

Language:English
Title:Calculation of the Kaplan turbine cooling system
Abstract:The objective was to determine the highest possible temperature of the Drava River at which the closed cooling system is still able to keep the aggregate below the critical temperature. By carrying out an analytical calculation, we checked the cooling ability of the most temperature-sensitive part of the turbine system (the carrier bearing) and proposed possible improvements based on the obtained results. The maximum temperature of the River Drava at which operating is still possible without any modification of the cooling system was found to be 22.5 °C. If the number of plates of the plate heat exchanger of the carrier bearing and the flow of the cooling liquid were increased, adequate cooling of the unit could be ensured even at a river water temperature of 24 °C.
Keywords:Kaplan turbine, closed cooling system, plate heat exchanger