Title:Procedure for the determination of the appropriate protective foil size to reduce step voltage using a FEM model and evolutionary methods
Authors:ID Jesenik, Marko (Author)
ID Kitak, Peter (Author)
ID Maruša, Robert (Author)
ID Ribič, Janez (Author)
Files:.pdf applsci-15-04611.pdf (29,51 MB)
MD5: 36CF8DAFECC696D20308122B55F44107
 
Language:English
Work type:Article
Typology:1.01 - Original Scientific Article
Organization:FERI - Faculty of Electrical Engineering and Computer Science
Abstract:When a fault occurs in a power transmission system, voltages that are dangerous to people may occur. The aim of this work is to present the following method of protection: the use of protective foil installed at the appropriate depth around the transmission pole. Moreover, a procedure is presented for determining the optimal size of the protective film using a minimum number of finite element method calculations. In addition to the finite element method, evolutionary methods are used to determine the appropriate coefficients. Real earthing system data, earth data, and the fault current are obtained from the Slovenian system operator (ELES, d.o.o.) and used exclusively in the presented analyses. The results of determining the appropriate size of the protective foil for two transmission poles are presented, and the determination of the required breakthrough strength of the materials used is shown. The suitability of the proposed method is confirmed. This method is practical and useful when protection with protective foil is required, ensuring only as much as necessary is applied.
Keywords:transmission system, touch voltage, touch voltage, step voltage, grounding system, differential evolution, artificial bee colony, teaching–learning-based optimization
Publication status:Published
Publication version:Version of Record
Submitted for review:16.04.2025
Article acceptance date:18.04.2025
Publication date:22.04.2025
Publisher:MDPI
Year of publishing:2025
Number of pages:32 str.
Numbering:Vol. 15, iss. 9, [article no.] 4611
PID:20.500.12556/DKUM-92596 New window
UDC:621.3
ISSN on article:2076-3417
COBISS.SI-ID:233961731 New window
DOI:10.3390/app15094611 New window
Copyright: © 2025 by the authors
Publication date in DKUM:23.04.2025
Views:164
Downloads:11
Metadata:XML DC-XML DC-RDF
Categories:Misc.
:
Copy citation
  
Average score:(0 votes)
Your score:Voting is allowed only for logged in users.
Share:Bookmark and Share



Hover the mouse pointer over a document title to show the abstract or click on the title to get all document metadata.

Record is a part of a journal

Title:Applied sciences
Shortened title:Appl. sci.
Publisher:MDPI
ISSN:2076-3417
COBISS.SI-ID:522979353 New window

Document is financed by a project

Funder:ARIS - Slovenian Research and Innovation Agency
Project number:P2-0114-2020
Name:Aplikativna elektromagnetika

Licences

License:CC BY 4.0, Creative Commons Attribution 4.0 International
Link:http://creativecommons.org/licenses/by/4.0/
Description:This is the standard Creative Commons license that gives others maximum freedom to do what they want with the work as long as they credit the author.

Secondary language

Language:Slovenian
Keywords:prenosni sistemi, stopenjska napetost, napetost dotika, diferencialna evolucija, umetna kolonija čebel